This is an example, laid out the way a paid report is delivered. The equipment, findings and companies are made up to show each section. A Scout Report for your own unit is researched for your equipment, your address and today's local prices — and is $4.99 per unit, or part of the plan.

HVAC Scout

HVAC SCOUT · EXAMPLE REPORT

Scout Report

HVAC diagnostic assessment

REPORT NO.
HS-20261103-YMVH
STATUS
Example only
EQUIPMENT
Rooftop / packaged · Rooftop unit RTU-3 · 10-ton gas/electric
LOCATION
Fort Worth, TX, 76102
SYMPTOM REPORTED
Warm air on the 2nd floor, high-pressure lockout code, economizer stuck open
PREPARED
Nov 3, 2026
PRINCIPAL FINDING

Dirty condenser coil and a failed economizer actuator on RTU-3

Recommended action
Repair the unit
Urgency
Book a repair this week
Repair estimate
$2,700 – $3,675
Replacement estimate
$31,250 – $38,400

1Summary

RTU-3 is tripping on high head pressure because the condenser coil is loaded with debris, and the economizer is stuck open, pulling in hot outside air. The job spans HVAC and controls: clean the coil and replace the actuator first, then the controls tech re-tunes the economizer setpoints.

2How urgent is this

Book a repair this week

Leave it running in cooling mode, but close the economizer in the BAS if you can so it stops pulling in hot outside air.

If you wait: Repeated high-pressure trips wear the compressor. A compressor replacement on a 10-ton RTU runs $9,350–$13,200, against about $3,300 for this repair.

3Safety notices

  • Roof access only with fall protection and the unit locked out at its disconnect.

4Likely causes

Most likely50%+Possible20–49%Less likelyunder 20%
  1. 1
    Dirty condenser coilMost likely55%

    High-pressure lockouts on a hot afternoon with a coil that hasn't been washed this season. A coil wash and a pressure check confirm it.

  2. 2
    Economizer actuator failed openPossible30%

    A damper stuck open brings in 95°F outside air, so the unit can't keep up. The actuator is checked against its 2–10 V control signal.

  3. 3
    Condenser fan motor or capacitorLess likely15%

    A weak condenser fan also raises head pressure; the amp draw is checked during the visit.

The causes listed add up to 100%, weighed on the symptoms, the equipment and its age.

5Cost analysis

REPAIR, FOR THIS FAULT

$2,700 – $3,675

Condenser coil wash, economizer actuator, roof access with fall protection, and a controls technician for 4–8 hours to re-commission the economizer and BAS points.

REPLACEMENT, INSTALLED

$31,250 – $38,400

10-ton gas/electric RTU, curb adapter, crane lift, permit, start-up, and controls integration with the building automation system.

Get a second opinion on any repair quote above $4,450.

That is well above the normal range for this repair in your area.

A FAIR WRITTEN QUOTE FOR THIS REPAIR LISTS
  • Condenser coil wash (chemical and rinse)
  • Economizer actuator by part number
  • HVAC labor and roof access or fall-protection charge
  • Controls technician hours to re-commission the economizer and BAS points
  • Trip charge per visit

Availability notice

  • Model no longer current
  • R-410A refrigerant

Availability can change this price. These ranges assume the part, the equipment and the refrigerant can be bought at today's prices. A discontinued model, a part that is scarce or no longer made, or a phased-out refrigerant can raise the cost and lengthen the wait. Confirm price and availability with the contractor before you approve the work.

Installed figures in USD for Fort Worth, TX — estimates, not a quotation.

6Recommendation

What could tip this toward replacement
  • Model no longer current

    This RTU series has been superseded by an R-454B model; the economizer actuator is cross-referenced to the current part.

  • R-410A refrigerant

    R-410A is being phased down, so its price per pound climbs every year. A repair that needs a charge carries a cost that keeps coming back.

None of this changes what the repair costs today — it changes whether the repair is worth doing. With these on the record a repair loses at 40% of the replacement price, rather than the usual 50%.

VERDICTRepair the unit

The $3,675 high repair is about 12% of the low replacement price, and the unit is 9 years into a typical 15–20-year rooftop life. Repair it now and add coil cleaning and economizer checks to the PM agreement so it doesn't happen again.

7Check these yourself first3 quick checks before anyone comes outShow
  1. 1Note the exact alarm code on the thermostat or BAS screen.
  2. 2Photograph the RTU-3 data tag and the condenser coil face.
  3. 3Ask the PM provider when the coils were last washed.
8Before you call a contractorWhat to say, and 4 questions to askShow
WHAT TO TELL THEM

“RTU-3, a 10-ton gas/electric rooftop unit from 2017, is tripping on a high-pressure lockout on hot afternoons, and the 2nd floor is getting warm air. The economizer damper looks stuck open. We don't have a record of a coil wash this season.”

QUESTIONS TO ASK
  1. 1What were the head pressure and the condenser fan amp draws before and after the coil wash?
  2. 2Is the replacement actuator a direct OEM part or a cross-reference, and does it accept our 2–10 V control signal?
  3. 3Will your controls tech or ours re-commission the economizer, and is that time included?
  4. 4Is the compressor still inside its separate warranty term, given the 2017 install?
9Local companiesCovering Fort Worth, TXShow
  • Sample: Trinity Mechanical ServicesIN THE NETWORK
    (817) 555-0119

    Fort Worth · Responds in within 4 hours, 24/7 · 4.7/5 (96) · Insured

FOUND ON THE WEB — CHECK THE LICENSE AND INSURANCE
  • Sample: Metroplex Commercial HVAC

    (817) 555-0174 · 4.5/5 (64) · Google · commercial, rooftop units, controls, 24/7 emergency service

10If you replace itReplacement choices and what each costsShow
Same or similar unit availableOriginal model: Replaced by a newer generation of the same line

A current 10-ton gas/electric rooftop unit fits the existing curb with an adapter and keeps the building's economizer and BAS integration. New units use an A2L refrigerant, so the curb adapter, startup and controls integration are part of the swap.

  • Carrier WeatherMaker rooftop unit

    Size
    10 ton
    Refrigerant
    R-454B
    Efficiency
    IEER per DOE 2023 minimums or better

    Same brand line as the unit on record; curb adapters are readily available.

  • Trane Precedent rooftop unit

    Size
    10 ton
    Refrigerant
    R-454B
    Efficiency
    IEER per DOE 2023 minimums or better

    Common replacement in this size range with broad local distributor support.

  • Lennox Energence rooftop unit

    Size
    10 ton
    Refrigerant
    R-454B
    Efficiency
    High-efficiency option

    A higher-efficiency alternative where utility rebates offset the price.

Examples found online for comparison, not an endorsement. The installed replacement range above covers a unit of this class; the contractor confirms the exact model, size and availability.

11Warranty checkWhat may still be coveredShow

Commercial parts terms are often only 1 year, but many rooftop units carry a separate 5- or 10-year compressor term. An economizer actuator and a coil wash are not covered, but ask about the compressor before any future repair.

12Your equipmentBrand, model, size and age on recordShow
MAKE AND MODELRooftop unit RTU-3 10-ton gas/electric
AGE9 yrs
LIFE USED50% of a 18-year expected life · about 9 yrs left
CAPACITY10 tons
REFRIGERANTR-410A — being phased down; prices rising
WARRANTY ON FILEPartly covered (a component term may still run)
13Keep it from coming back5 steps for this unit and siteShow
  • Rinse the outdoor coil each springCottonwood fluff mats the coil from April to July. A gentle hose rinse from the inside out, with the power off, keeps it breathing through the season.
  • Protect the coil from hailAsk about hail guards, straighten bent fins with a fin comb, and photograph storm damage — it may be an insurance claim.
  • Keep ants out of the outdoor unitBait around the pad in spring and fall. Ants packed into the contactor are a common reason a unit won't start here.
  • Add surge protectionAsk for a surge protector at the outdoor disconnect during this visit. Storm surges take out boards, capacitors and compressors.
  • Check the other units on this propertyUnits of the same age and make on the same roof tend to fail the same way. Have them looked at on this visit.
14Scope of workWhich trades the job needsShow
  • HVAC
    Wash the condenser coil, test the condenser fans, and replace the economizer actuator.
    Refrigerant-side work and the rooftop unit itself.
  • Controls
    Re-commission the economizer: changeover setpoint, minimum outside air and the BAS points.
    The building automation system owns the damper logic and setpoints.

A job spanning these trades is coordinated work: expect separate visits, a permit for each trade that needs one, and a schedule where the first trade has to finish before the next starts.

15Terms used in this reportPlain meanings for the trade words above. Tap to openShow

Plain meaning first; tap a term for the technician's wording.

Ton (tonnage)
A measure of cooling power, not weight. One ton cools about as much as a small apartment; three tons is common for a whole house.
Tech
12,000 BTU/h of cooling capacity. Residential equipment runs 1.5–5 tons; nameplate model numbers usually encode it (24 = 2 tons, 36 = 3 tons).
BTU/h
How much heat the system moves in an hour. A bigger number means more capacity, and more electricity or gas to run it.
Tech
British thermal units per hour. 12,000 BTU/h = 1 ton. Capacity on a nameplate is almost always rated at a specific indoor and outdoor condition.
SEER2
The cooling efficiency score. A higher number costs more upfront and less every summer.
Tech
Seasonal Energy Efficiency Ratio, 2023 test procedure. Federal minimum is 14.3 SEER2 for most of the US; some southern regions require higher.
HSPF2
The heating efficiency score for a heat pump, in the same spirit as SEER2 for cooling.
Tech
Heating Seasonal Performance Factor, 2023 procedure. Higher is better; 8.5+ HSPF2 is efficient in most markets.
Refrigerant (R-410A, R-454B, R-32)
The fluid inside the sealed circuit that carries heat. The type matters: a change in refrigerant can mean a new coil and line set rather than a swap.
Tech
R-410A is being phased down under the AIM Act; R-454B and R-32 are the lower-GWP replacements and are mildly flammable (A2L), which adds handling and charge-limit duties.
Compressor
The pump at the heart of the system. It is the most expensive single part and the usual reason a repair costs more than half a new unit.
Tech
Scroll or reciprocating pump that raises refrigerant pressure between the evaporator and condenser. Replaced only with the refrigerant recovered, a new filter-drier, and a documented charge.
Capacitor and contactor
Small electrical parts that start the motor. Cheap to replace, and a common reason a unit hums but will not start.
Tech
The run/start capacitor stores the phase shift a single-phase motor needs; the contactor is the relay that switches the compressor and fan. Both fail on age and heat, and both are stock parts.
Blower and air handler
The fan that pushes air through the ducts, and the box it sits in. A slow fan shows up as weak airflow and a warm house.
Tech
The air handler contains the blower wheel, the evaporator coil, and often the electric heat strip. Airflow is set by blower taps and must match the outdoor unit's required CFM per ton.
Static pressure
How hard the fan has to push. Too high means the ducts are too small or clogged, and the system loses capacity even when nothing is broken.
Tech
Measured in inches of water column (in. w.c.) across the air handler. External static above roughly 0.8 in. w.c. on residential equipment points to duct restriction, an undersized filter, or a coil that needs cleaning.
Condensate drain
The pipe that carries the water the system pulls out of the air. Blocked, it backs up and can shut the unit off or damage the ceiling.
Tech
Condensate must run to a trapped drain with fall; a float switch or overflow pan protects the space. A dry trap on a negative-pressure coil prevents drainage entirely.
Refrigerant charge, superheat and subcooling
How much refrigerant is in the circuit. Low charge is the difference between a system that cools and one that runs constantly and never gets there.
Tech
Verified by superheat (fixed orifice) or subcooling (TXV) against the manufacturer's charging chart, with indoor wet-bulb and outdoor dry-bulb recorded. Never topped up without finding the leak.
TXV (thermostatic expansion valve)
The valve that meters refrigerant into the coil. Stuck, it starves or floods the coil.
Tech
The metering device at the evaporator inlet; set by superheat. A power head or bulb failure reads as a flooded or starved coil and is confirmed against a charging chart.
Defrost cycle
A heat pump periodically melts frost off its outdoor coil. Running it in cold weather is normal; never stopping can mean a stuck sensor or reversing valve.
Tech
Initiated by the defrost board from coil and ambient sensors; failure to terminate or too-frequent initiation shows as low capacity, ice on the outdoor coil, and high head pressure.
Short cycling
Starting and stopping every few minutes. It wears parts out and usually means the unit is oversized, overcharged, or starved of airflow.
Tech
Cycling faster than the thermostat's minimum off time. Causes: oversized capacity, a fouled filter or coil, low charge with a high-pressure cutout, or a failing control board.
Installed price
The number that matters: equipment plus labor, materials, and startup, not the sticker on the box.
Tech
Equipment, labor, line sets and piping, electrical, controls, permits where they apply, recovery and disposal, and commissioning. Excludes financing, abatement, and structural or utility-side work.
HVAC SCOUT · EXAMPLE ONLY · NOT ISSUED · EXAMPLENOT ISSUED
EXAMPLE — NOT AN ISSUED REPORT

This example shows the layout and the sections of a Scout Report. A Scout Report for your own unit is researched for that equipment, its address and current local prices.

REPORT NO.
HS-20261103-YMVH
STATUS
Example only

Estimate only — not a quote, an inspection or professional advice. Have a licensed HVAC contractor confirm the problem and the price before you buy anything or approve work. Refrigerant, gas and electrical work require a licensed technician.

SCOUT REPORT · HS-20261103-YMVHEXAMPLE ONLY — NOT ISSUED FOR A REAL UNIT

Want this for your own unit?

Price my own unit — one report is $4.99